1 Installation/Operator’s Manual 1 Rev: February, 02-20-2006 THIS MANUAL SUPERCEDES ALL PREVI
DUCTING PRIMARY FURNACE To install the GBU070 as a “Primary Furnace” first locate the furnace as near the chimney and as cent
ELECTRICAL REQUIREMENTS 1. Make sure that the power source conforms to the requirements of the furnace. Disconnect the power source before perfor
TURNING OFF THE UNIT Turn the power switch to draft fan. Fuel will stop feeding but the draft fan will remain running. Let run until fire burns ou
BURNING CORN IN THE GBU070 NOTE: If your 070 was purchased as a corn unit the corn pot should already be installed. The corn pot utilizes a lift o
11. Let the pot cool completely to the touch and place into a bucket of water to dissolve the clinker. DO NOT PLACE HOT POT IN WATER;
START UP INSTRUCTIONS – PELLET Now that your furnace has been properly installed, it’s time to fire it up! 1. Plug in the furnace. NOTE: Make su
START UP INSTRUCTIONS – CORN NOTE: Pellets are required to start your initial fire. 14. Plug in the furnace. NOTE: Make sure you plug into a pro
PRIMARY CONTROL OII 350S SEQUENCE OF OPERATION The Traeger OII 350S primary control is a high-tech, state of the art computer. Th
TROUBLE SHOOTING GUIDE Tools Essential for Trouble Shooting 1. Furnace Installation and Operation manual 2. Circuit Tester / Volt Meter 3. Mo
STEP 3# CONFIRM DRAFT FAN OPERATION Be sure the main power switch is in the “Draft Fan” position. This will cause the draft fan to operate at full p
TABLE OF CONTENTS FURNACE SPECIFICATIONS pg 2 CONTROL AND COMPONENT FUNCTIONS pg 3 GENERAL INSTRUCTIONS pg 4-5 CLEARANCE TO COMB
INSTALLATION/ADJUSTMENT RELATED PROBLEMS PROBLEM: Incomplete combustion, unburned fuel. SOLUTION: 1. Adjust air shutter to a more open position
OPERATOR RELATED PROBLEMS cont’d PROBLEM: Furnace will not feed fuel. SOLUTION: Check for blockage in metering cup. Is there fuel in the hopper?
#10. The blower cycles on and off too much. CHECK CAUSES: 9, 12, 22 or 59. #11. Furnace burns without regard to thermostat, overheats. CHECK CAUSES:
3. An impurity in the pellets has hung up the auger. Remedy: The cup is turning but the auger is not. Loosen the coupling on the auger and try to tur
16. Improper stove ground. Remedy: Check the ground. Check the outlet. Just because there is a three-prong outlet receptacle does not mean that there
28. Too much chimney draft. Remedy: Check draw with a draft gauge. Maximum draft .08 inches. If draw exceeds .08 reduce chimney outlet to accomplish.
43. Undersized or overloaded service wiring. Remedy: Call your electrical contractor. 44. Power surge. Remedy: Call your electrical contractor. 45.
59. Aluminum air filter is dirty. Remedy: Remove from furnace and wash. 60. Inadequate return air. Too small, restricted, or is pulling unconditione
PARTS LIST 1. Hopper connector flange F000221P 8. Cup motor F000101P 2. Pillow block ball bearing F000505P
WARRANTY NON TRANSFERABLE MODEL: _GBU070___________ SERIAL NUMBER: ____________________ DATE PURCHASED: __________________ FROM: ____
FURNACE SPECIFICATIONS HEIGHT--------------------------------------------------- 45 ¼ WIDTH---------------------------------------------------- 2
CONTROL AND COMPONENT FUNCTIONS AUGER The auger transfers the pellet fuel from the hopper end of the burner tube down and into the fire pot. AUGER
GENERAL INSTRUCTIONS 1. Installation is allowed only by a licensed, bonded heating contractor. 2. Install this furnace in accordance with local
19. Doors and heat exchanger surfaces of the furnace are hot during operation. DO NOT touch with bare hands, or allow children to play near the fur
CLEARANCE TO COMBUSTIBLES 6
CHIMNEY AND VENTING Chimney required for the GBU070 is 4” Class “L” (also known as PL vent). A starting collar must be used to attach the venting
VERTICAL CHIMNEY’S The chimney that this unit is connected to (Class “L”, all fuel or masonry) should extend above the roofline of adjacent build